This article provides technical specifications, installation guidance, and sizing information for the FLEXECHARGE Dynamic Load Management (DLM) Hardware Package.
Dynamic Load Management Hardware Package
Typical installation locations
- GATEWAY & power supply: Central network location, typically in a network cabinet next to the Ethernet switch.
- Antenna: Route the 5 m cable to the best LTE reception point (outside wall, as high as possible). Avoid metal cabinets, indoor locations, or underground rooms.
- Own router scenario: If a customer uses their own router, the antenna is not required. GATEWAY, router, charging stations, and power meter must be connected to the same local network.
- Power meter: DIN-rail mounted in a distribution cabinet close to the measuring point. Rogowski coils are installed directly on the measured power line.
The power meter’s point of measurement can later be configured in HARMON-E, allowing the EMS to correctly interpret the received measurement.
GATEWAY
The GATEWAY is the local controller for Dynamic Load Management with HARMON-E. It collects measurement data, executes local control logic, and communicates with the backend. The GATEWAY continues to operate and enforce grid limits even when cloud connectivity is unavailable.
| Power supply | 8…30 V DC |
| Max. power consumption | 25 W |
| Interfaces | |
| Ethernet | 1 × 10/100 Mbit/s |
| USB | USB 2.0 |
| SIM | 2 × Mini-SIM (1.8 V / 3.3 V) |
| Antenna GSM | 1 × SMA socket, impedance 50 Ω |
| Mechanical | |
| Dimensions (H × W × D) | 119 × 27 × 105 mm |
| Mounting | DIN rail |
Power Supply
| Model | UNO-PS/1AC/24DC/60W |
| Output | 24 V DC, 60 W |
| Mechanical | |
| Dimensions (W × H × D) | 35 × 90 × 84 mm |
| Mounting | DIN rail (TS-35) |
Antenna (GSM)
The antenna connects to the GATEWAY via the SMA port. Use the 5 m cable to route the antenna to a location with strong LTE reception. If the customer uses their own router, the antenna is not required.
| Supported networks | 2G / 3G / 4G / LTE |
| Cable length | 5 m |
| Connector | SMA (to GATEWAY) |
Power Meter
The EEM-MA371 is a multifunctional power meter for low-voltage installations. It measures electrical parameters via Rogowski coils and provides the data to the GATEWAY via Modbus/TCP.
| Manufacturer | Phoenix Contact |
| Product type | EEM-MA371 |
| Communication | Modbus/TCP |
| Electrical specifications | |
| Supply voltage range | 100…240 V AC |
| Input voltage signal | 24 V DC |
| Current transformers | Rogowski coils |
| Mechanical | |
| Dimensions (H × W × D) | 90 × 90 × 71.7 mm |
| Mounting form | DIN rail |
Rogowski Coils
| Electrical | |
| Insulation | Double insulation |
| Rated insulation voltage |
1000 V AC (rms) CAT III 600 V AC (rms) CAT IV |
| Frequency measuring range | 40 Hz … 20000 Hz |
| Mechanical | |
| Length | 450 mm |
| Diameter | 8.3 mm ±0.2 mm |
| Diameter when installed | 140 mm |
| Signal line | |
| Length | 3 m |
| Ambient conditions | |
| Degree of protection (measuring coil) | IP54 (not assessed by UL) |
| Ambient temperature (operation) | −30 °C … 80 °C (measuring coil) |
| Ambient temperature (storage/transport) | −40 °C … 80 °C (measuring coil) |
Measurement range & sizing guidance
- The power meter itself does not limit the measurable current.
- The maximum measurable power depends on the selected Rogowski coils.
- With typical 1000 A Rogowski coils, grid connections up to approximately 700 kW can be measured at 400 V.
- Smaller grid connections (e.g. 50 kW) are well within range.
- For grid connections above 1 MW, higher-rated Rogowski coils or an alternative metering solution may be required.